Offices, people, and code · guide
Stair rise and run: the guide
A stair is a count of equal risers under a maximum height, with treads at least a minimum depth, and the two codes that apply to a plant disagree on both numbers.
Why this number matters
The building code's stair, the one on an exit path, has risers no taller than 7 inches and treads no shallower than 11, which makes a 12-foot floor-to-floor a 21-riser stair with 18 feet of run plus landings. OSHA's industrial stair, for equipment access and the stairs employees use that are not required exits, allows 9.5-inch risers and 9.5-inch treads, 16 risers and 12 feet of run for the same rise. Ship stairs and alternating-tread stairs are steeper still and allowed only where the mezzanine serves equipment or very few people.
The risers must be equal to within 3/8 inch, so the count is the rise over the maximum rounded up, and the riser is the rise over that count. The 17.5 to 18 inch rule, riser plus tread, keeps the stair comfortable; landings every 12 feet of rise break a long flight, and the width is 36 inches under 50 occupants and 44 above, 22 for an OSHA stair.
Which code applies is the question to settle first. If the mezzanine is a required exit or is open to the staff generally, the building official will inspect to the IBC; most mezzanine makers quote an IBC stair unless told otherwise.
How it is figured
- Risers = total rise ÷ the maximum riser, rounded up, all equal. IBC 1011.5: riser 4 to 7 in., tread 11 in. minimum; the 25 in. rule (riser + tread about 17 to 18) sets a comfortable tread. OSHA 1910.25: riser 9.5 in. max, tread 9.5 in. min, 30 to 50° pitch.
- Run = treads × tread depth; stringer = √(rise² + run²). Landings every 12 ft of vertical rise (IBC 1011.8).
A worked example
A 12-foot floor-to-floor under the IBC takes 21 risers of 6.86 inches, 20 treads at 11 inches for 220 inches of run, a 263-inch stringer at 32 degrees, and no intermediate landing; under OSHA it takes 16 risers of 9 inches and 142 inches of run.
The tool's starting values, and what it returns for them:
| Floor to floor | 12' 0" |
| Stair type | IBC egress stair: 7 in. max riser, 11 in. min tread |
| Stair width | 44 in |
| Risers | 21 |
| Total run | 220 in |
| Stringer length | 263 in |
| Riser height | 6.86 in |
| Tread depth | 11 in |
| Intermediate landings | 0 |
| Footprint with a bottom landing | 22'-0" long x 3'-8" wide |
Mistakes that catch people
- Quoting an OSHA stair on an exit path.
- A bottom riser that takes up the leftover: all risers equal.
- Forgetting the landing at the top, which is the mezzanine width, and the one at the bottom, which is the stair width.
Rules of thumb
- IBC: 7-inch riser max, 11-inch tread min, 44 inches wide over 49 occupants.
- OSHA 1910.25: 9.5-inch riser max, 9.5-inch tread min, 30 to 50 degrees.
- Landing every 12 feet of rise; headroom 6'-8".
When to stop calculating and make a call
- Every mezzanine stair on a permit: the official decides IBC or OSHA.
- Alternating-tread and ship stairs: the exception has conditions.
Questions people ask
- IBC or OSHA for a mezzanine stair?
- If the mezzanine is a required exit path or is open to employees generally, the building code (IBC) governs and the official inspects to it; OSHA's 9.5 in. riser applies to stairs serving equipment and maintenance. Most mezzanine makers quote IBC stairs and OSHA only where the customer confirms it.
Standards and sources
- IBC 2021 Section 1011 (stairways)
- OSHA 29 CFR 1910.25 (stairways, standard, ship, and alternating tread)
This guide and the tool are planning aids. The equipment maker, the engineer of record, the accountant, or the code official confirms the final number for your building.