Material handling and racking
Mezzanine floor load and column loads
Mezzanine size, the use, and the column grid in; the design live load, the total load, and what each column puts on the slab.
Read the guide: what the number means and how to use it
- Live load from the use (IBC Table 1607.1: offices 50 psf, light storage 125, heavy storage 250) plus about 15 psf dead load for the deck and framing.
- An interior column carries its tributary area (column spacing each way) times the total load; base plate pressure is that over the plate area. Edge and corner columns carry half and a quarter.
Need it quoted?
Guardrail, bollards, rack protection, and mezzanines priced as line items.
Guardrail and protectionMezzanine floor and column loads
Design live load
125 psf
plus 15 psf for the deck and steel
Load on an interior column
42,000 lb
300 sq ft tributary
Pressure under the base plate
292 psi
- 292 psi under the base plates is more than a 6 in. slab on grade usually takes without footings; the mezzanine maker's engineer will call for a slab check or pads.
- Total design load
- 168,000 lb
- Columns
- 93 × 3 grid
- Area
- 1,200 sq ft
One line for the file or the vendor
40x30 ft mezzanine at 125 psf live + 15 psf dead, columns 20x15 ft (9): interior column 42000 lb, 292 psi on a 144 sq in plate.
How it is figured
- Live load from the use (IBC Table 1607.1: offices 50 psf, light storage 125, heavy storage 250) plus about 15 psf dead load for the deck and framing.
- An interior column carries its tributary area (column spacing each way) times the total load; base plate pressure is that over the plate area. Edge and corner columns carry half and a quarter.
Sources: IBC Table 1607.1, minimum uniformly distributed live loads; Mezzanine manufacturer design practice (Cogan, Wildeck, Steele Solutions). A planning calculator; the maker, the engineer of record, or the code official confirms the final number.
Questions people ask
- What live load should I specify?
- 125 psf covers most storage and pick modules and is the common quote basis; offices need 50 but are usually built at 125 anyway so the space can change use; pallets staged on the deck need 250 and heavier framing.
Related calculators: Pallet rack beam and frame loads, Stair rise and run, Guardrail take-off. All calculators.