Modular cleanroom: what plant buyers need to know

Reviewed October 16, 2026. Official sources are linked where they exist.

Short answer

A modular cleanroom is a room built inside your plant from wall and ceiling panels, with HEPA fan filter units in the ceiling and a controlled pressure difference to the plant, that holds a cleanliness class under ISO 14644-1. The class is a particle count: at 0.5 micron and larger, ISO 8 allows 3,520,000 particles per cubic metre, ISO 7 allows 352,000, ISO 6 allows 35,200 and ISO 5 allows 3,520. The class sets the air: ISO 14644-1 does not state air changes, but the FDA's aseptic processing guidance accepts at least 20 air changes per hour for ISO 8 support rooms and notes that ISO 7 and ISO 5 need significantly more, and it calls for a positive pressure of at least 10 to 15 pascals between rooms of differing class with the doors closed. Most plant cleanrooms for assembly, packaging, medical device and electronics work are ISO 7 or ISO 8; ISO 5 and ISO 6 are pharmaceutical and semiconductor territory. Send the class you need, the floor plan and what will run inside, and you get a 3D rendering, shop drawings and a bill of material before the purchase order. Freight to your dock is included.

The class is a particle count, and it drives everything else

ISO 14644-1 classifies air by the number of particles of a given size in a cubic metre. The 2015 edition is current. The table below uses the 0.5 micron column that most plant specifications quote, together with the old Federal Standard 209E class names that are still spoken on the floor. The class is tested in a stated occupancy state: as built, at rest, or operational with people and process running. A room that holds ISO 7 empty can run ISO 8 with six people in it, so the specification states the class and the state together.

Which class you need comes from the product and the customer, not from the room supplier. Medical device makers under 21 CFR 820 and ISO 13485 commonly specify ISO 7 or ISO 8 for assembly and packaging. Electronics, optics and precision assembly often land at ISO 7. Sterile drug products under 21 CFR 211 and the FDA aseptic guidance need ISO 5 at the point of fill with ISO 7 and ISO 8 around it. A food or nutraceutical packaging line may need only a controlled, filtered, positive-pressure room without a certified class at all, and that is a cheaper room.

ISO 14644-1 classes at 0.5 micron and larger, as tabulated in the FDA aseptic processing guidance
ISO 5 (Class 100)3,520 particles per cubic metre
ISO 6 (Class 1,000)35,200 particles per cubic metre
ISO 7 (Class 10,000)352,000 particles per cubic metre
ISO 8 (Class 100,000)3,520,000 particles per cubic metre
Typical plant uses, ISO 7 and 8Medical device assembly and packaging, electronics, optics, precision assembly
ISO 5 and 6Sterile fill, pharmaceutical compounding, semiconductor

Air changes, filters and the pressure cascade

Clean air comes from HEPA filters, rated to remove 99.97 percent of 0.3 micron particles, mounted in fan filter units in the ceiling. The number of units sets the air change rate and the ceiling coverage. ISO 14644-1 sets particle limits, not air changes, so the rate is a design choice tied to the class, the people and the process. Design guides published by the cleanroom trade give ranges rather than a single value: roughly 5 to 60 air changes per hour for ISO 8, 60 to 150 for ISO 7, 150 to 240 for ISO 6, and 240 or more for ISO 5, with the ranges differing from one guide to the next. The FDA guidance for sterile products says at least 20 air changes per hour is typically acceptable for ISO 8 supporting rooms and that significantly higher rates are needed for ISO 7 and ISO 5. For unidirectional flow at an ISO 5 work zone the same guidance gives a velocity of 0.45 metres per second, plus or minus 20 percent.

Pressure is the other half. The cleanest room sits at the highest pressure and air flows outward toward the plant, so contamination cannot drift in. The FDA guidance gives at least 10 to 15 pascals, which is 0.04 to 0.06 inches of water gauge, between adjacent rooms of differing classification with the doors closed. That cascade is why a cleanroom is usually more than one room: a gowning room or an anteroom at an intermediate pressure stands between the plant and the clean space, with interlocked doors so both are never open at once. Return air leaves through low wall grilles so the room washes top to bottom. Pressure is monitored continuously with a gauge at the door and an alarm.

Temperature and humidity ride along with the air. Gowned people are warm, and 60 or more air changes an hour of HEPA-filtered air needs a cooling coil sized for it. The HVAC package is quoted as its own line and is the largest item in many cleanroom bills of material.

Softwall, hardwall or modular panel: three constructions

A softwall cleanroom is a frame with clear vinyl strip curtains or panels hanging from a filter ceiling. It is the fastest and least expensive way to reach ISO 7 or ISO 8 over a bench or a small line, it moves easily, and it leaks air by design, so it cannot hold a tight pressure cascade or a humidity setpoint. A hardwall cleanroom replaces the curtains with rigid panels, usually acrylic, polycarbonate or coated steel in an aluminum frame, and holds pressure and class more reliably. A modular panel cleanroom is built like an in-plant office: insulated wall and ceiling panels with flush, sealed joints, coved corners, flush windows and lights, and a load-bearing ceiling that carries the fan filter units and gives a walkable plenum. It is the construction for ISO 5 through ISO 7, for multi-room cascades, and for any room that an auditor will walk.

Whatever the shell, the surfaces are the same: non-shedding, hard, smooth, cleanable with the agents the process uses, no ledges that hold dust. Floors are seamless vinyl or epoxy with a coved base, by others or on the bill of material. Doors are flush with sweeps and interlocks. Pass-through chambers move parts in and out without opening a door. Lighting is flush and sealed. Everything that penetrates the envelope, from power to compressed air to data, comes through sealed fittings.

  • Softwall: curtains on a frame, ISO 7 to 8, fast and relocatable, no real pressure control
  • Hardwall: rigid panels in a frame, ISO 6 to 8, holds pressure and humidity
  • Modular panel room: insulated sealed panels, load-bearing ceiling, ISO 5 to 8, multi-room cascades, audit ready
  • All three: HEPA fan filter units in the ceiling, low wall returns, interlocked doors, pass-throughs
  • Floors, fire sprinklers and the main HVAC connection are usually by others and are shown on the drawings

The rules that may apply, and who decides

For a sterile drug product, 21 CFR 211.42(c)(10) requires that aseptic processing areas have floors, walls and ceilings of smooth, hard surfaces that are easily cleanable, temperature and humidity controls, an air supply filtered through HEPA filters under positive pressure, and a system for monitoring environmental conditions. The FDA aseptic processing guidance of 2004 is the reference most pharmaceutical quality managers hand to a room supplier. For medical devices, the quality management system regulation in 21 CFR 820, which incorporates ISO 13485, requires you to control the environment where it could affect product quality, and the class comes out of your own risk assessment.

ISO 14644 is a series. Part 1 is classification, Part 2 is monitoring, Part 3 is test methods, and Part 4 is design, construction and start-up. After installation a third-party certifier tests the room for particle counts, airflow, filter integrity and pressure in the stated state and issues the certificate your customer or auditor asks for. Certification is a separate line from the room. The building official rules on the construction questions, including sprinklers under the solid ceiling, egress from a room with interlocked doors, and electrical, and the drawings are what the permit office reviews.

How we quote a modular cleanroom

Send the ISO class and the state it must hold (at rest or operational), the process and the equipment that will run inside with its heat load, the number of people at peak, a floor plan or a photo of the location with the clear height, how many rooms the cascade needs (gowning, anteroom, clean space), the utilities that have to penetrate the envelope, and the regulatory context, whether 21 CFR 211, 21 CFR 820 and ISO 13485, or an internal specification. We return a 3D rendering of the rooms in your space, a shop drawing set with the panel layout, doors, pass-throughs, filter unit positions and returns, and a component bill of material with the HVAC package and third-party certification on their own lines. Freight to your dock is included in the quotation. Non-sealed drawings are standard; PE-stamped drawings for your state are a separate line.

Questions buyers ask

What is the difference between a cleanroom and a controlled environment?
A cleanroom is certified to an ISO 14644-1 class in a stated state and tested by a third party. A controlled environment is filtered, positive-pressure and clean, but no class is claimed. If your customer does not require a class, the controlled room costs less.
Does an ISO 8 cleanroom need HEPA filters?
Yes. The class is reached by diluting and sweeping particles with HEPA-filtered air; the fan filter unit count is lower than for ISO 7, but the filters are the same. The FDA guidance accepts at least 20 air changes per hour for ISO 8 support rooms in sterile manufacturing.
Softwall or hardwall?
Softwall for a bench or a small line at ISO 7 or 8 that may move, where pressure and humidity do not matter. Hardwall or a modular panel room where you need a pressure cascade, humidity control, a multi-room layout or an audit trail.
Can a modular cleanroom be moved or expanded?
Yes. Panels unbolt, and the ceiling grid, filter units and doors are reused. The HVAC connection and the floor are the parts that stay. Expansion is a matter of adding panels and filter units and recertifying.
Who certifies the room?
An independent cleanroom certifier, after start-up, testing particle counts, airflow, filter integrity and pressure in the state your specification names. It is a separate line on the quotation and the certificate is what your auditor sees.

Do your own research