Cleanrooms: a room built to a class, on your floor, with a door that keeps it there.

A cleanroom is a specification before it is a room: a particle count per cubic meter at a stated class, an air change rate that achieves it, a pressure relationship to the rooms around it, and a way in and out that does not break any of that. Modular cleanrooms meet the specification on an existing plant floor, from panels and a ceiling grid, with the fan filter units and the lighting in the grid and the doors and pass-throughs in the walls.

The first 3D example on our home page is exactly that: an ISO Class 7 cleanroom on a plant floor with a high-speed door and an airlock. Spin it, step inside, and then send us your floor plan.

Cutaway drawing of a modular training room with rows of tables and chairs facing a screen

Representative drawing of the equipment type, not the exact configuration quoted.

Reviewed November 4, 2026. Official sources are linked where they exist.

Short answer

A plant that needs a cleanroom buys a modular hardwall or softwall cleanroom built to an ISO 14644-1 class (ISO 7 and ISO 8 are the common plant classes), with fan filter units in a ceiling grid for the air changes, a pressure cascade to the rooms around it, a gowning room and an airlock at the entrance, pass-through chambers for parts, high-speed roll-up doors with tight seals where carts and forklifts enter, cleanroom-compatible benches and chairs, and guardrail outside the walls where the plant's forklifts run. The class, the air changes, the pressure, and the entrance sequence are decided from the process, then the room is drawn on your floor plan and quoted with a 3D rendering and drawings before the order.

What this facility buys from us

The class decides the room

ISO 14644-1 classes are particle counts per cubic meter at a particle size. ISO 8 is the loosest commonly specified; ISO 7 is the usual plant cleanroom for medical device assembly, electronics, optics, and precision packaging; ISO 5 and tighter are laminar flow spaces that are designed differently. The class drives the air change rate, the filter coverage in the ceiling, the pressure, and the finishes. The cleanroom guide works through the classes and the numbers for a plant buyer.

Common plant cleanroom classes, planning view
ISO 8Low particle counts for packaging, kitting, and light assembly; moderate air changes, partial filter ceiling coverage, positive pressure to the plant
ISO 7Medical device, electronics, optics; higher air changes, more filter coverage, a gowning room and an airlock, pass-throughs for parts
ISO 6 and tighterHigher coverage and air changes, stricter gowning, often a separate HVAC design; a different conversation from a plant-floor modular room

Air, pressure, and the way in

Fan filter units in the ceiling grid push HEPA-filtered air down; return air leaves through low wall returns or the gap under softwall curtains. The pressure in the room is higher than the plant so air leaks out, not in, and a gowning room sits between them with a pressure step. Every opening is a leak, which is why doors matter: a high-speed roll-up door with a sealed perimeter is open for seconds and closed tight; an interlocked airlock keeps two doors from opening at once; a pass-through chamber moves parts without opening either.

  • Fan filter units: count and placement from the class and the room volume
  • Pressure: positive to the plant, stepped down through the gowning room and the airlock
  • People: gowning room, interlocked airlock doors, sticky mats, benches on the clean side
  • Material: pass-through chambers with interlocked doors, a high-speed door for carts and forklifts
  • Monitoring: a differential pressure gauge at the entrance, and particle counting at commissioning

Hardwall or softwall

A hardwall cleanroom is panels on a track with a solid ceiling grid, windows, and doors; it holds pressure, takes a high-speed door, and can be rated for fire. A softwall cleanroom is a frame with clear vinyl curtains and the same ceiling grid; it is cheaper, goes up faster, and suits ISO 8 and some ISO 7 applications where a cart has to pass through the curtain. Most plant cleanrooms for production are hardwall; most for staging and inspection are softwall.

What else goes in and around it

The room is only part of the quotation.

  • Gowning room with lockers, a bench, a mirror, and a garment rack
  • Pass-through chambers in the wall, sized for the trays or totes
  • Cleanroom benches, chairs, and shelving that wipe down and do not shed
  • Lighting in the ceiling grid, receptacles and data in the panels, a pressure gauge at the door
  • A high-speed door for the material entrance, with the columns protected by bollards or guardrail on the plant side
  • Guardrail along the cleanroom wall where forklifts travel, with gaps at the doors

Standards and rules

The class standard plus whatever the product is regulated under.

  • ISO 14644-1 for the classification and ISO 14644-2 for monitoring
  • FDA current good manufacturing practice (21 CFR 210 and 211 for drugs, Part 820 for devices) where the product is regulated
  • The customer's quality system and audit requirements, which usually specify the class and the gowning
  • OSHA 1910 Subpart D and 1910.178 for the plant side of the wall
  • Local building and fire codes for the room as a structure and for its materials

What to send

The process and the floor plan.

  • The ISO class required, or the product and process so we can propose one
  • Floor plan with the location marked, the clear height, and the ceiling obstructions
  • Head count inside, and the gowning level the quality system requires
  • Material flow: what comes in and out, how, and how often
  • Power location and whether the room's HVAC ties into the plant or stands alone
  • The delivery ZIP code

Questions buyers ask

What ISO class do I need?
It comes from the product and the customer's specification. ISO 7 is the common plant class for medical devices and electronics; ISO 8 covers packaging and kitting. The cleanroom guide explains the classes; send the process and we propose one.
Can a cleanroom have a forklift door?
Yes. A high-speed roll-up door with a sealed perimeter and an airlock or a vestibule on the plant side keeps the pressure while the forklift passes. The home page example shows it.
How long does a modular cleanroom take?
Factory lead time of several weeks for the panels and the grid, then days to a couple of weeks on site depending on size, followed by balancing and particle counting.
Do you certify the cleanroom?
The room is built to the class and balanced; certification testing is by a third-party certifier, which we can arrange with the installation.
Can installation be on the quotation?
Yes. Tick "Quote installation too" and a cleanroom-experienced installer from our network prices the assembly, the ceiling grid, and the fan filter units from the same drawings.

Do your own research

Official sources first. We link the rule, not a summary of the rule, wherever one exists.

Guides for this facility

Work it out

Free calculators for the numbers this decision turns on, each with a guide to the method.